What is a chiller?
A chiller is an industrial refrigeration machine that uses a vapour-compression cycle to cool a liquid — most often water or a water–glycol mixture — to the required temperature and deliver it to a process or to air-handling units. It removes heat from the liquid and rejects it to the surroundings.
A chiller does not cool air by itself; it cools water (or a water–glycol mixture). The chilled water travels through pipes to the process, to fan coils or to air-handling units and returns warmer. This is why it is used as a central cooling solution wherever the heat load is continuous and large.
Where are chillers used?
- Cooling of plastic injection moulding and extrusion tooling
- Food and beverage processes
- Chemical and pharmaceutical manufacturing
- Data centres and cold storage halls
- Central air conditioning in large buildings
- Applications with a continuous heat load, such as biogas plants, freeze-drying and concrete batching plants
How does a chiller work?
Every chiller runs a vapour-compression refrigeration cycle made up of four main components.
- 01
Evaporator
The refrigerant evaporates here and absorbs heat from the warm water returning from the process. The chilled water is sent back to the process.
- 02
Compressor
Compresses the low-pressure refrigerant vapour, raising its pressure and temperature. It can be a scroll, screw, reciprocating or centrifugal type.
- 03
Condenser
The hot, compressed vapour condenses as it rejects its heat to outdoor air (air-cooled) or to condenser water (water-cooled).
- 04
Expansion valve
Reduces the pressure of the condensed liquid and meters the flow. The refrigerant re-enters the evaporator and the cycle repeats.
For details on compressor types, see our refrigeration compressors catalogue.
Air-cooled vs. water-cooled chillers
The key difference between the two types is where the heat is rejected. Your site's water infrastructure, capacity and operating conditions determine the choice.
| Feature | Air-cooled | Water-cooled |
|---|---|---|
| Where the heat is rejected | Outdoor air, via fans | Condenser water (via a cooling tower, dry cooler or a water source) |
| Installation | Installed as a single unit outdoors or on a roof; no condenser water circuit required | Needs additional equipment such as a tower, pumps and a water circuit; installation is more extensive |
| Water consumption | None | Evaporation losses and water treatment are required if a cooling tower is used |
| Efficiency | Depends on outdoor air temperature; capacity and efficiency can drop in hot weather | Generally more efficient, especially at high capacities and under continuous load |
| Maintenance | Condenser coil cleaning and fan checks | Condenser tube cleaning, plus water treatment and cooling tower maintenance |
| Typically suited to | Small to medium-capacity sites without a water source, or where quick installation is needed | Large capacities, continuous loads and sites with water infrastructure |
How is chiller capacity calculated?
Capacity is the heat load that must be removed from the process. From flow rate and temperature difference it can be estimated in practice as follows:
Q (kW) ≈ 1.163 × Flow (m³/h) × ΔT (°C)
A practical formula derived from the specific heat of water (about 4.18 kJ/kg·K) and its density (about 1,000 kg/m³).
Worked example
- Suppose 20 m³/h of water circulates in your process, entering the chiller at 12 °C and leaving at 7 °C (ΔT = 5 °C).
- Q ≈ 1.163 × 20 × 5 ≈ 116 kW
- That is roughly 100,000 kcal/h (1 kW ≈ 860 kcal/h), or about 33 tons of refrigeration (1 TR ≈ 3.517 kW).
Points to note
- If you use a water–glycol mixture instead of water, the specific heat and density change, and so does the result.
- The value you calculate is the process heat load. When selecting a chiller, check the operating conditions (outdoor air or condenser water temperature, required leaving water temperature) against the manufacturer's capacity table.
- Include simultaneous loads, planned growth and, where needed, redundancy (N+1) in the capacity.
Checklist for selecting a chiller
Having this information ready when you request a quote lets us identify the right unit faster.
- 1Process heat load (kW) and flow rate / temperature difference (entering and leaving water)
- 2Required leaving water temperature and, if needed, glycol concentration
- 3Environment: maximum year-round outdoor air temperature and installation space (outdoors, roof, plant room)
- 4Water source and cooling tower availability (decides between air-cooled and water-cooled)
- 5Compressor type: scroll, screw, reciprocating or centrifugal (according to capacity and load profile)
- 6Refrigerant (e.g. R134a, R410A, R513A, R1234ze) and applicable regulations
- 7Electrical infrastructure: supply voltage, frequency, installed power
- 8Redundancy and continuity requirements (downtime tolerance), spare parts and service access
New, used, rental or overhauled
Solutions that vary with your needs:
New and in-stock systems
Our air-cooled and water-cooled chiller catalogue includes new, used and remanufactured options.
Chiller catalogue →Chiller rental
Rental for emergency breakdowns, seasonal loads or temporary cooling for the duration of a project.
Chiller rental →Chiller overhaul
Renewing the compressor, controls and heat exchanger components of your existing chiller to extend its service life.
Chiller overhaul →Service and maintenance
Periodic maintenance, fault repair and commissioning services.
Service and maintenance →For more information, see our articles on industrial chiller maintenance and the chiller rental guide.
Frequently asked questions about chillers
What is a chiller?
A chiller is an industrial refrigeration machine that cools a liquid (usually water or a water–glycol mixture) and delivers it to a process. It works with a refrigeration cycle made up of a compressor, condenser, expansion valve and evaporator.
What is the difference between a chiller and an air conditioner?
An air conditioner cools air directly. A chiller cools water, which is piped to fan coils, air-handling units or process equipment. That is why chillers are the preferred central solution in large buildings and for process cooling.
Should I choose an air-cooled or a water-cooled chiller?
If you have no water source or cooling tower and want a quick, simple installation, an air-cooled chiller is generally suitable. For large capacities and continuous loads, a water-cooled system is generally more efficient if you have water infrastructure. The final decision depends on ambient temperature and operating cost.
How is chiller capacity determined?
It is based on the process heat load, the required water temperature and the flow rate. Practical calculation: Q (kW) ≈ 1.163 × Flow (m³/h) × ΔT (°C). The result should be verified against the manufacturer's capacity table for your operating conditions.
Why is chiller maintenance important and what does it involve?
Condenser fouling, refrigerant level and pressure deviations reduce efficiency and increase the risk of failure. Periodic maintenance includes condenser cleaning, refrigerant and pressure checks, and inspection of electrical and safety components. The maintenance interval depends on operating conditions.
Should I replace an old chiller or overhaul it?
If the casing and heat exchangers are sound, overhauling the compressor and control components is often faster and more economical than buying a new unit. The condition of the unit, the capacity requirement and whether the refrigerant is still current should be assessed together; contact us for a free preliminary assessment.