The Shift to Liquid Cooling: How Chiller Architecture Is Changing in AI Data Centres

For twenty years, data centre cooling rested on an unchanged equation: produce chilled water, transfer it to the air through the CRAH, and blow that air onto the rack. AI hardware has made this equation physically invalid. The question is no longer "how many tonnes of chiller do we need" but "at which point does the heat transfer to water".
This article looks at what liquid cooling changes in mechanical installations, how it redefines chiller selection criteria, and which decisions operators should take now, amid the wave of investment in Türkiye.
Where does the physical limit of air cooling end?
Power density per rack has, on its own, upset the capacity planning habits of the industry:
- 2020 average: approximately 8.4 kW per rack
- H100-class GPU rack: approximately 40 kW
- Practical ceiling of air cooling: approximately 20 kW per rack
- Rear-door heat exchanger (RDHx): 20–80 kW range, ~75 kW with active doors
- GB200 NVL72-class rack: 120–132 kW, of which approximately 115 kW is rejected directly into the liquid
The gap is not a matter of incremental improvement. Taking the airflow that cools an 8 kW rack to 120 kW means moving fifteen times more air in the same volume. Fan power rises with the cube of the airflow; at this point the fans themselves become a significant part of the load that has to be cooled.
The Uptime Institute's 16th Global Data Center Survey of 2026 (more than 800 operators) shows a rapidly growing number of operators reporting peak rack densities of 30 kW and above. In other words, this is not only a problem for hyperscale players; colocation and enterprise data centres are approaching the same threshold.
Liquid cooling architecture: TCS and FWS loops
In direct-to-chip solutions, the system is split into two separate water loops, and this separation directly determines chiller selection.
TCS — Technology Cooling System loop
This is the closed loop that leaves the CDU and runs to the cold plates inside the rack. The fluid is either treated water or 25% propylene glycol, in line with the IT manufacturer's specification. The supply temperature is set by the maximum inlet temperature the chip permits. On the NVIDIA MGX platform this limit goes up to 45 °C; in the GB200 example the fluid returns at 65 °C, meaning a temperature rise of about 20 K across the loop.
FWS — Facility Water System loop
This sits on the other side of the CDU and carries the heat to a dry cooler, cooling tower or chiller. A typical design uses 40 °C supply / 50 °C return, i.e. a 10 K difference.
The approach temperature of the CDU, which separates the two loops, is the key design parameter. Manufacturers generally quote 2–5 K; for example, 4 K is declared for the Vertiv CoolChip CDU 2300. Allowing a total of 3–5 K including the rise in the distribution lines, supplying facility water at roughly 40–42 °C is sufficient for a 45 °C chip inlet limit.
Why does the flow calculation shrink?
A liquid load of 920 kW requires a flow of about 22.2 L/s at a 10 K temperature difference. If the same load is designed with a 15 K difference, the flow drops to 14.8 L/s. Because increasing delta-T reduces pump power, pipe diameter and valve cost together, the first optimisation item in liquid cooling projects is almost always the temperature difference.
ASHRAE W classes: the threshold that takes the chiller out of service
The economic case for liquid cooling stems from the ability of facility water to operate at high temperatures. The ASHRAE classification defines this as follows:
| Class | Max. supply water | Typical heat rejection method |
|---|---|---|
| W17 | 17 °C | Chiller + cooling tower, compressor-dominated |
| W27 | 27 °C | Chiller + tower, limited economiser hours |
| W32 | 32 °C | Tower or hybrid, chiller for backup only |
| W40 | 40 °C | Dry cooler or adiabatic assist, chiller rarely |
| W45 | 45 °C | Dry cooler, chiller only on extremely hot days |
| W+ | Above 45 °C | Dry/evaporative/hybrid, mechanical cooling when needed |
The critical point is this: in W40 and higher designs, the chiller ceases to be the primary equipment and becomes reserve capacity. In locations with high summer design temperatures such as Adana, Mersin or İzmir, this "rarely" must be verified hour by hour with climate data; the bin counts of European reference projects are not directly valid in Türkiye.
On the other hand, high-temperature operation has a price: the thermal margin remaining to the chip limit narrows, and the stored chilled water available to carry the system through a heat rejection failure is reduced. For this reason, in W40/W45 designs an N+1 heat rejection path and uninterruptedly powered CDU pumps are not a point of debate but a necessity.
Mixed load: a single chiller is no longer enough
In an AI hall, not all of the heat goes to the liquid. In a typical split, 70–90% of the rack load (varying by platform) goes to the cold plates, while the remainder (power supplies, networking equipment, memory modules) is still released to the air. Electrical rooms, UPS halls and office areas are added to this.
The result is two different temperature regimes living in the same facility:
- High-temperature loop (W40+): a dry cooler, or a dry cooler with adiabatic pre-cooling, for the liquid load
- Chilled water loop (6–12 °C): for air handling units, rear-door heat exchangers and electrical rooms
In practice, this means chiller capacity is selected not against the total IT load but only against the share left to air. A selection made on the total load, out of old habit, produces an oversized plant that runs continuously at part load and shortens compressor life. We covered the capacity determination method in detail in our cooling capacity calculation guide; in liquid-cooled halls this calculation has to be done separately for the two loops.
The picture in Türkiye: infrastructure decisions are being made now
According to the target announced by Minister of Industry and Technology Mehmet Fatih Kacır in October 2026, Türkiye's installed data centre capacity will be raised to at least 1 gigawatt by 2030. The scale of the announced investments is as follows:
- Ankara Temelli facility: USD 450 million investment, 22 MW capacity
- Rönesans–Digital Realty partnership: a target of 200 MW with approximately USD 3 billion
- Planned private-sector investment in data centre, cloud and AI infrastructure through 2030: more than USD 10 billion
- HIT-Data Centre Call: USD 1.5 billion support budget, for facilities with a minimum capacity of 30 MW
What these figures mean for mechanical installations is clear: the majority of facilities coming online over the next four years must be designed to be liquid-cooling-ready from day one. A hall designed today with air cooling alone will lose its commercial value, since it will be unable to accept GPUs within three years.
A decision framework for operators
If you are designing a new facility
Separate the chilled water and high-temperature loops from the start. Reserve pipe shafts, riser areas and CDU placement areas while there is still no liquid load; adding them later is the most expensive work that can be done in a live hall.
If you have an existing facility
The first step is the rear-door heat exchanger. It covers the 20–80 kW per rack range using your existing chilled water infrastructure and does not change the hall architecture. Above 80 kW, direct-to-chip becomes unavoidable.
If a chiller replacement decision is approaching
Before replacing an end-of-life plant with one of identical capacity, model the load distribution three years from now. Because the air-side load will fall as you move to liquid cooling, the new plant needs to be smaller but with a wider capacity modulation range. In this scenario, a variable-speed compressor and broad part-load efficiency matter more than nominal COP.
Frequently asked questions
Does liquid cooling eliminate the need for a chiller entirely?
No. Even if the liquid load can be handled by a dry cooler in the W40/W45 class, chilled water is still needed for air handling units, electrical rooms and rear-door heat exchangers. The chiller's role shifts from primary equipment to support/backup equipment, and its capacity shrinks.
Can my existing chilled water system be used for direct-to-chip?
Technically yes, but it would be inefficient. Feeding 7 °C chilled water to a loop that can operate at 40 °C means running the compressor unnecessarily. The correct approach is to connect the facility side of the CDU to a separate high-temperature loop.
Will a dry cooler be sufficient in Turkish climate conditions?
It depends on the location. For a 40 °C facility water target, the outdoor air temperature must remain below the target by at least the dry cooler's approach temperature. In regions with high summer design temperatures such as Adana, adiabatic pre-cooling or chiller support for limited hours comes into play. The decision should be based on a bin analysis using hourly climate data.
Is CDU maintenance different from chiller maintenance?
The emphasis shifts. For a chiller, the compressor and refrigerant circuit come first; for a CDU, water chemistry, filter differential pressure and plate heat exchanger fouling come to the fore. In the TCS loop, conductivity and particle control are critical because they prevent cold plate blockage. Our periodic maintenance checklist needs to be extended with water chemistry items for liquid-cooled facilities.
Conclusion
Liquid cooling has turned the capacity question in data centre mechanical design into a temperature question. The right question is no longer "how many kW of cooling do we need" but "at what temperature can I capture and reject the heat". Facilities that can answer this question at high temperature permanently reduce their compressor hours and therefore their operating costs.
At Özsayın Soğutma, we provide engineering support in data centre projects on high-temperature loop design, chiller capacity modelling and adapting existing plants to mixed loads. Contact us to review the load distribution of your project together.